2. Commissioning
Selecting station
Entering device name
Festo P.BE−CPX−PN IO−EN en 0710NH
3. In the Hardware Catalogue, open the directory:
\PROFINET−IO\Additional Field Devices\Valves\
Festo CPX−Terminal"
(English language version of the software)
or
\PROFINET−IO\Weitere Feldgeräte\Ventile\
Festo CPX−Terminal
If the directory Valves\Festo CPX−Terminal" (Ventile\
Festo CPX−Terminal) is not displayed, repeat the installa
tion of the device master file (GSDML, see section Instal
ling GSDML file).
4. Drag the CPX" station symbol on to the bus line of the
PROFINET IO system (2 in Fig. 2/2).
The CPX terminal is displayed as a symbol (3 see also
Tab. 2/5) and connected to the bus of the PROFINET IO
system.
5. Double click on the symbol of the CPX terminal 3.
The Properties CPX" window is displayed see Fig. 2/3).
You can assign or change a device name for the CPX ter
minal in the next step. This device name is also stored on
the memory card (provided it is inserted) of the bus node.
Using this device name, you can also directly Address"
the CPX terminal, e.g. in automation programs. Alterna
tively, you can also use the IP address or the MAC−ID for
addressing (information about IP addressing can be
found in the following steps).
If you have allocated a device name in the course of
identifying the CPX terminal, you can skip the next step.
2−17