B.4.2 System Object (For Operating Mode Remote I/O) - Festo CPX-FB32 Electronic Manual

Cpx field bus node, field bus protocol ethernet/ip
Hide thumbs Also See for CPX-FB32:
Table of Contents

Advertisement

B. Ethernet/IP Objects of the CPX−FB32

B.4.2 System Object (for operating mode Remote I/O)

Attr.
Access Description
no.
1
Get
CPX operating mode (bit 0...3)
0: Remote I/O without FEC
1: Remote I/O with FEC
2: Remote Controller without bus node
3: Remote Controller with bus node
CPX equipment status (bit 4)
Specifies whether the current equipment fitted to the
CPX corresponds to the saved CPX equipment status.
0: equal
1: not equal
Handheld (bit 5)
Specifies whether or not a handheld is connected.
0: Handheld not connected
1: Handheld connected
Force mode (bit 6)
Specifies whether Force is blocked or enabled.
0: blocked
1: enabled
Bit 7: Reserved
2
Get
Fail safe
Specifies whether Fail safe is active or inactive.
0: inactive
1: active
System Idle mode
Specifies whether Idle mode is active or inactive.
0: inactive
1: active
B−16
Object class:
132
Instances:
1
This Object is only available in the operating mode Remote
I/O.
Type
Function
no.
BYTE
0 (bit 0...3)
0 (bit 4)
0 (bit 5)
0 (bit 6)
0 (bit 7)
BYTE
1 (bit 0, 1)
1 (bit 2, 3)
Festo P.BE−CPX−FB32−EN en 0605NH

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents