Configure Response Time Parameters; Configure Alert Handling; Configure Fault Timeout - Emerson Micro Motion 2700 Configuration And Use Manual

With foundation fieldbus
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Configure device options and preferences
5.4

Configure response time parameters

You can configure the rate at which process data is polled and process variables are
calculated.
5.5

Configure alert handling

The alert handling parameters control the transmitter's response to process and device
conditions.
5.5.1

Configure Fault Timeout

Display
ProLink III
Field Communicator Configure > Alert Setup > Alert Severity > Fault Timeout
Fieldbus host
Overview
Fault Timeout controls the delay before fault actions are performed.
Restriction
Fault Timeout is applied only to the following alerts (listed by Status Alert Code): A003, A004, A005,
A008, A016, A017, A033, A036. For all other alerts, fault actions are performed as soon as the alert is
detected.
Procedure
Set Fault Timeout as desired.
The default value is 0 seconds. The range is 0 to 60 seconds.
If you set Fault Timeout to 0, fault actions are performed as soon as the alert condition is
detected.
The fault timeout period begins when the transmitter detects an alert condition. During
the fault timeout period, the transmitter continues to report its last valid measurements.
If the fault timeout period expires while the alert is still active, the fault actions are
performed. If the alert condition clears before the fault timeout expires, no fault actions
are performed.
64
Not available
Device Tools > Configuration > Fault Processing
Diag TB > LAST_MEASURED_VALUE_FAULT_TIMEOUT (OD Index 22)
Micro Motion Model 2700 Transmitters with FOUNDATION Fieldbus