Configure Gas Standard Volume Flow Cutoff - Emerson Micro Motion 2700 Configuration And Use Manual

With foundation fieldbus
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Configure process measurement
The special measurement unit is stored in the transmitter. You can configure the
transmitter to use the special measurement unit at any time.
Example: Defining a special measurement unit for gas standard volume flow
You want to measure gas standard volume flow in thousands of standard cubic feet per
minute.
1.
2.
3.
4.
5.
6.
4.3.4

Configure Gas Standard Volume Flow Cutoff

Display
ProLink III
Field Communicator Configure > Manual Setup > Measurements > GSV > GSV Cutoff
Fieldbus host
Overview
Gas Standard Volume Flow Cutoff specifies the lowest gas standard volume flow rate that
will reported as measured. All gas standard volume flow rates below this cutoff will be
reported as 0.
Procedure
Set Gas Standard Volume Flow Cutoff to the value you want to use.
The default value for Gas Standard Volume Flow Cutoff is 0.0. The lower limit is 0.0. There
is no upper limit. The recommended value is 0.5% of the nominal flow rate of the attached
sensor. See the sensor specifications.
30
Set Base Gas Standard Volume Unit to SCF.
Set Base Time Unit to minutes (min).
Calculate the conversion factor:
a. 1 thousands of standard cubic feet per minute = 1000 cubic feet per minute
b. Gas Standard Volume Flow Conversion Factor = 1 ÷ 1000 = 0.001 standard
Set Gas Standard Volume Flow Conversion Factor to 0.001.
Set Gas Standard Volume Flow Label to MSCFM.
Set Gas Standard Volume Total Label to MSCF.
Not available
Device Tools > Configuration > Process Measurement > Flow
Measurement TB > SNS_GSV_FlowCutoff (OD Index 74)
Micro Motion Model 2700 Transmitters with FOUNDATION Fieldbus