FOUNDATION
fieldbus function blocks
C.3.6

INT block special mode

Enhanced FF host
Fieldbus Host
Along with standard operation of integrating the process value at INn, the Micro Motion
Integrator function block has one special mode of operation: Input 1 pass through. In this
special mode of operation, the device internal totals/inventories are controlled through
the Integrator block. The Integrator block passes through the device total/inventory to
output and the device total/inventory is reset by the RESET_IN input. To control the
integrator block mode there is one additional parameter in the Total-Inventory TB for each
INT block. By default the integrator function block operates in standard mode.
Fieldbus
code
0
1
2
3
4
5
6
7
8
9
10
292
Overview > Totalizer Control > Configure Integrator Block
Measurement TB > INTEGRATOR_FB_CONFIG (OD Index 50)
Label
Description
Standard
Block is working as per configuration of function block parame-
ters.
Internal Mass To-
Block outputs internal mass total value and RESET_IN resets inter-
tal
nal mass total
Internal Volume
Block outputs internal volume total value and RESET_IN resets in-
Total
ternal volume total
Internal Mass In-
Block outputs internal mass inventory value and RESET_IN resets
ventory
internal mass inventory
Internal Volume
Block outputs internal volume inventory value and RESET_IN re-
Inventory
sets internal volume inventory
Internal Gas
Block outputs internal gas standard volume total value and RESET_
Standard Volume
IN resets internal gas standard volume total
Total
Internal Gas
Block outputs internal gas standard volume inventory value and
Standard Volume
RESET_IN resets gas standard volume inventory and internal API:
Inventory
temp corrected volume inventory
Internal API:
Block outputs internal API: temp corrected volume total value and
Temp Corrected
RESET_IN resets internal API: temp corrected volume total
Volume Total
Internal API:
Block outputs internal API: temp corrected volume inventory value
Temp Corrected
and RESET_IN resets gas standard volume inventory and internal
Volume Inventory
API: temp corrected volume inventory
Internal ED:
Block outputs internal ED: standard volume total value and RESET_
Standard Volume
IN resets internal ED: standard volume total
Total
Internal ED:
Block outputs internal ED: standard volume inventory value and
Standard Volume
RESET_IN resets internal ED: standard volume inventory
Inventory
Micro Motion Model 2700 Transmitters with FOUNDATION Fieldbus