Table A-4:
Process variables for measurement transducer blocks
Index and name
#41
FLOW_DIRECTION
#42
HIGH_MASS_LIMIT
#43
HIGH_TEMP_LIMIT
#44
HIGH_DENSITY_LIMIT
#45
HIGH_VOLUME_LIMIT
#46
LOW_MASS_LIMIT
#47
LOW_TEMP_LIMIT
Configuration and Use Manual
Description
Flow direction
Msg type = ENUM
Data type = Unsigned16 (2)
Store = Static
Access = RW in any mode
Available in Release 1.0
High mass flow limit of sensor
Msg type = VAR
Data type = FLOAT (4)
Store = Static
Access = Read only
Available in Release 1.0
High temperature limit of sensor
Msg type = VAR
Data type = FLOAT (4)
Store = Static
Access = Read only
Available in Release 1.0
High density limit of sensor in g/cc
Msg type = VAR
Data type = FLOAT (4)
Store = Static
Access = Read only
Available in Release 1.0
High volume flow limit of sensor
Msg type = VAR
Data type = FLOAT (4)
Store = Static
Access = Read only
Available in Release 1.0
Low mass flow limit of sensor
Msg type = VAR
Data type = FLOAT (4)
Store = Static
Access = Read only
Available in Release 1.0
Low temperature limit of sensor
Msg type = VAR
Data type = FLOAT (4)
Store = Static
Access = Read only
Available in Release 1.0
(continued)
List of values
0 = Forward Only
1 = Reverse Only
2 = Bi-Directional
3 = Absolute Value
4 = Negate/Forward Only
5 = Negate/Bi-Dir
Transducer blocks and views
HW
700
800
CDM
700
800
700
800
CDM
FDM
FVM
700
800
CDM
FDM
FVM
700
800
700
800
700
800
CDM
FDM
FVM
141