The special unit label displays only on the local display. The AI block uses and displays the actual
engineering unit (i.e. L/min).
Procedure
1.
2.
3.
4.
5.
6.
The special measurement unit is stored in the transmitter. You can configure the
transmitter to use the special measurement unit at any time.
Example: Defining a special measurement unit for volume flow
You want to measure volume flow in pints per second (pints/sec).
1.
2.
3.
4.
5.
6.
4.2.3

Configure Volume Flow Cutoff

Display
ProLink III
Field Communicator Configure > Manual Setup > Measurements > Flow > Volume Flow Cutoff
Fieldbus host
Configuration and Use Manual
Specify Base Volume Unit.
Base Volume Unit is the existing volume unit that the special unit will be based on.
Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
Calculate Volume Flow Conversion Factor as follows:
a. x base units = y special units
b. Volume Flow Conversion Factor = x ÷ y
Enter Volume Flow Conversion Factor.
The original volume flow rate value is divided by this conversion factor.
Set Volume Flow Label to the name you want to use for the volume flow unit.
Set Volume Total Label to the name you want to use for the volume total and
volume inventory unit.
Set Base Volume Unit to Gallons (gal).
Set Base Time Unit to Seconds (sec).
Calculate the conversion factor:
a. 1 gal/sec = 8 pints/sec
b. Volume Flow Conversion Factor = 1 ÷ 8 = 0.1250
Set Volume Flow Conversion Factor to 0.1250.
Set Volume Flow Label to pints/sec.
Set Volume Total Label to pints.
Not available
Device Tools > Configuration > Process Measurement > Flow
Measurement TB > VOLUME_FLOW_LOW_CUTOFF (OD Index 39)
Configure process measurement
25