Example Connection Of An Msi 100/200 System; Figure 7-7 Msi 100/200 System Voltage Supply - Leuze electronic MSI 200 Series User Manual

Configurable safety modules and safe extension modules
Table of Contents

Advertisement

F1
230 V
+
-
24 V
Leuze electronic
7.4.3

Example connection of an MSI 100/200 system

Note the following points when connecting your MSI 100/200 system to the various partici-
pants:
Voltage supply and ground reference
Supply the supply voltage for all other devices participating in the system via the same
voltage supply.
Only use power supply units with safe insulation and SELV/PELV in accordance with
EN 50178 / VDE 0160.
Safeguard the voltage supply externally with a suitable fuse.
Connect the output-side GND connection of the power supply unit to the functional earth
(FE) of the system.
Ensure that all inputs and outputs of the system are connected to the same ground.
Other participants
For the connection of safe extension modules, use only the yellow MSI-TBUS DIN rail con-
nector.
For the connection of non-safe extension devices (gateways), use only the green TBUS
DIN rail connector.
The following figure shows the correct connection of the voltage supply for an MSI 100/200
system with various participants.
MSI 200
Figure 7-7
MSI 100/200 system voltage supply
Legend:
External fuse
F1
Functional earth (FE)
Mounting, removal and electrical installation
MSI‐EM200‐
8I4IO
MSI 100/200
MSI‐EM200‐4RO
72