Leuze electronic MSI 200 Series User Manual page 109

Configurable safety modules and safe extension modules
Table of Contents

Advertisement

General specifications
Maximum number of safe extension modules in the MSI 100/200 system
Maximum number of non-safe extension devices (gateways) in the
MSI 100/200 system
Maximum continuous current via MSI-TBUS
Dimensions and weight
Width / height / depth
Weight with plugs
Dimensions and connection data
Conductor cross-section (rigid/flexible)
Stripped length
Screw thread
Tightening torque
UL note:
To maintain UL approval, use copper cables that are designed for operating temperatures of > 75 °C.
Environmental conditions
Ambient temperature
Operation
Storage/transport
Air humidity
Operation
Storage/transport
Air pressure
Operation
Storage/transport
Operation altitude
Shock
Vibration (operation)
Leuze electronic
10
1
4 A
Screw connection
22.5 mm / 99 mm / 114.5 mm
Approx. 130 g
Screw connection
0.2 mm² ... 2.5 mm²
AWG 24 ... 12
7 mm
M3
0.5 Nm ... 0.6 Nm
5 lb in ... 7 lb in
- 20 °C ... + 55 °C (see Derating)
- 20 °C ... + 70 °C
75% (average, 85% occasionally)
75% (average, 85% occasionally)
70 kPa ... 108 kPa (up to 3000 m above sea level)
66 kPa ... 108 kPa (up to 3500 m above sea level)
Max. 2000 m above sea level
See appendix "Use of MSI 100/200 modules at altitudes above 2000 m above
sea level" on page 125
10g t = 11 ms (three shocks in each spatial direction)
10g t = 16 ms (continuous shock; 1000 shocks in each spatial direction)
2g
MSI 100/200
Technical data and ordering data
Spring-cage connection
22.5 mm / 112 mm / 114.5 mm
Approx. 130 g
Spring-cage connection
0.2 mm² ... 1.5 mm²
AWG 24 ... 16
8 mm
-
-
109

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents