Logic / supply
Rated control circuit supply voltage U
Permissible range
Rated control supply current I
S
Status indicator
Protective circuit
Safe relay outputs O0 to O3
Quantity
Info: The pairwise wiring of the relay outputs corresponds to the factory settings.
Pair 1: 13/14 and 23/24 (bridge between contacts 13/23)
Pair 2: 33/34 and 43/44 (bridge between contacts 33/43)
Type
Contact material
Switching voltage
Limiting continuous current
Switching current
Switching power
Life expectancy, mechanical
Output guarding
Status indicator
Signal outputs M0 to M3
Quantity
Type
Nominal voltage
Leuze electronic
14.3

Technical data MSI-EM200-4RO

S
24 V DC (supply via MSI-TBUS)
18 V DC ... 30 V DC
(incl. all tolerances, incl. residual ripple)
(Supply via MSI-TBUS)
74 mA 
(at 24 V DC, relay outputs set)
54 mA 
(at 24 V DC, relay outputs not set)
1 x green LED
1 x red LED
Yes, within the scope of the operating voltage limits
4 (one-channel)
2 (two-channel, pairwise wiring)
Relay contacts, safety-related normally open contacts
AgSnO
(from HW03)
2
AgCuNi + 0.2 - 0.4 μm Au (up to HW02)
Min. 12 V AC/DC (from HW03)
Min. 5 V AC/DC (up to HW02)
Max. 250 V AC/DC
4 A (see derating)
Min. 3 mA (from HW03)
Min. 5 mA (up to HW02)
Min. 60 mW
6
10 x 10
switching cycles
6 A gL/gG
4 A gL/gG (for low-demand applications)
4 x green LEDs
4
Digital
24 V DC (supply via A1/A2)
MSI 100/200
Technical data and ordering data