Initialization
Ending
data transmission
Leuze electronic
Following successful data transmission
–
The "CONF" status display flashes slowly on the safety module (approx. 1.5 Hz).
A corresponding dialog
–
"Sending successful" appears in the configuration software.
If the "Sending successful" dialog is displayed, perform the next steps in the following order.
Figure 10-5
Dialog box following successful data transmission
5.
Confirm the new configuration by pressing the "Confirm" button using a pen (see
Figure 10-6).
WARNING: Danger due to activated outputs
Following acknowledgment, the safety module starts running immediately. Provided that no
start interlock is active, which must be canceled manually, outputs may be activated imme-
diately after start-up.
Make sure that the start-up of the safety module cannot lead to any hazardous situa-
•
tions.
Figure 10-6
Confirming the configuration with the "Confirm" button
The safety module is then reinitialized (all diagnostic indicators illuminate briefly) and then
switches to safe normal operation (only "PWR" LED on).
6.
Exit the dialog in the configuration software and click on "OK".
Configuration and commissioning
Please note:
First acknowledge the configuration on
the safety module
(see step 5).
... before clicking "OK".
MSI 100/200