Maximum ambient temper-
ature
Derating curve
Switching voltage for relay
outputs
Leuze electronic
Use of MSI 100/200 modules at altitudes above 2000 m above sea level
A 3
Use of MSI 100/200 modules at altitudes above
2000 m above sea level
The following chapter describes the conditions for using modules of the MSI 100/200 system
at altitudes above 2000 m above sea level.
Observe the respective, specific data (technical data, derating, etc.) of the used module.
See "Technical data and ordering data" on page 101.
Use of the module at altitudes above 2000 m above sea level to max. 4500 m above sea
level is possible under the following conditions:
1.
Determine the maximum ambient temperature for operation with the corresponding factor
acc. to the following table.
2.
If a derating is specified, shift all points of the derating curve by the corresponding factor
according to the following table.
Operation altitude above sea level
2000 m
2500 m
3000 m
3500 m
4000 m
4500 m
3.
Limit the maximum switching voltage for relay outputs acc. to the following table. Note the
technical data of the device here.
Max. switching voltage acc. to the techni-
cal data of the device
< 150 V AC/DC
> 150 V AC/DC
Temperature derating factor
1
0.953
0.906
0.859
0.813
0.766
Max. switching voltage when used at alti-
tudes above 2000 m above sea level
Max. switching voltage acc. to the technical
data of the device remains valid
Limited to max 150 V AC/DC
MSI 100/200
125