Configuration
Difference in MSIsafesoft
Non-safe extension:
MSI 100/200
Safe extension: 
only MSI 200
Leuze electronic
The configuration of the safety modules is created with the MSIsafesoft configuration software.
You then load the configuration into the safety module via the USB interface.
WARNING: Non-safe operation
The USB interface is not protected against ESD. If a there is a USB connection in place, the
safety module is in non-safe operation. The safety function cannot be properly executed.
Only use the USB connection for commissioning.
Disconnect the USB connection for regular operation.
For the MSI 100 safety module, there are 16 external signals available in the MSIsafesoft con-
figuration software.
For the MSI 200 safety module, there are 64 external signals available. The use of diagnostic
addresses is also possible for function block diagnosis.
Further information on the MSIsafesoft configuration software can be found in Chapter
"MSIsafesoft configuration software" on page 75 or the help system of the software.
3.1.1

Connection of extension devices

Also read "Communication via the DIN rail connector" on page 16.
Connection of non-safe extension devices (gateways):
You can connect a maximum of one gateway to both safety modules for transferring diagnostic
data. Install the gateway to the left of the safety module.
Information on diagnosis via gateways can be found in the respective user manual of the
gateway. 
See www.leuze.com.
You can find suitable gateways for use with the MSI 100/200 system in the accessories chap-
ter "Gateways" on page 118.
Connection of safe extension modules:
Only the MSI 200 safety module can be extended with the safe extension modules of the 
MSI 100/200 system. Install a maximum of ten safe extension modules to the right of the
MSI 200 safety module.
Additional information on the safe extension modules can be found in chapters
"MSI-EM200-8I4IO safe extension module" on page 36 and "MSI-EM200-4RO safe exten-
sion module" on page 42.
MSI 100 and MSI 200 safety modules
MSI 100/200
25