14 Technical Data And Ordering Data; Technical Data Msi 100 And Msi 200 - Leuze electronic MSI 200 Series User Manual

Configurable safety modules and safe extension modules
Table of Contents

Advertisement

14 Technical data and ordering data

Logic / supply A1/A2
Rated control circuit supply voltage U
Permissible range
Rated control supply current I
S
Limiting continuous current
Filter time
Status indicator
Protective circuit
Safe digital inputs I0 to I19
Quantity
Type
Input voltage range "0" signal
Input voltage range "1" signal
Typical current consumption at U
Maximum total cable length
Status indicator
Safe digital outputs O0 to O3 and ground-switching outputs O0- and O1-
Quantity (type)
Nominal voltage
Permissible range
WARNING: Loss of the safety function
The use of unsuitable voltage supplies and the incorrect connection of the voltage supply can result in the loss
of the safety function.
Only use power supply units with safe insulation and SELV/PELV in accordance with EN 50178 /
VDE 0160.
Connect the output-side GND connection of the power supply unit to the functional earth (FE) of the system.
Leuze electronic

Technical data MSI 100 and MSI 200

14.1
S
S
24 V DC (A1/A2)
18 V DC ... 30 V DC
(incl. all tolerances, incl. residual ripple)
Typ. 110 mA
Max. 6 A 
(for looped-through current paths A1/A1 and A2/A2, see "Double terminal con-
tacts A1/A1 and A2/A2" on page 35)
Typ. 20 ms (load-dependent, on voltage dips for U
3 x green LEDs
1 x red LED
Yes, within the scope of the operating voltage limits
10 (two-channel, up to SIL 3)
20 (one-channel, up to SIL 2)
digital, type HTL
0 V DC ... 5 V DC (for safe off)
11 V DC ... 30 V DC
4 mA
2000 m
20 x green LEDs (1 LED per input)
4 (safe semiconductor outputs, up to Cat. 4 in accordance with EN ISO 13849-1)
2 (ground-switching outputs)
24 V DC (supply via 24V/0V)
18 V DC ... 30 V DC
(incl. all tolerances, incl. residual ripple)
MSI 100/200
Technical data and ordering data
)
S
101

Hide quick links: