Dimensions and weight
Width / height / depth
Weight with plugs
Dimensions and connection data
Conductor cross-section (rigid/flexible)
Stripped length
Screw thread
Tightening torque
UL note:
To maintain UL approval, use copper cables that are designed for operating temperatures of > 75 °C.
Environmental conditions
Ambient temperature
Operation
Storage/transport
Air humidity
Operation
Storage/transport
Air pressure
Operation
Storage/transport
Operation altitude
Shock
Vibration (operation)
Leuze electronic
Screw connection
22.5 mm / 99 mm / 114.5 mm
Approx. 140 g
Screw connection
0.2 mm² ... 2.5 mm²
AWG 24 ... 12
7 mm
M3
0.5 Nm ... 0.6 Nm
5 lb in ... 7 lb in
- 20 °C ... + 55 °C (see Derating)
- 20 °C ... + 70 °C
75% (average, 85% occasionally)
75% (average, 85% occasionally)
70 kPa ... 108 kPa (up to 3000 m above sea level)
66 kPa ... 108 kPa (up to 3500 m above sea level)
Max. 2000 m above sea level
See appendix "Use of MSI 100/200 modules at altitudes above 2000 m above
sea level" on page 125
10g t = 11 ms (three shocks in each spatial direction)
10g t = 16 ms (continuous shock; 1000 shocks in each spatial direction)
2g
MSI 100/200
Technical data and ordering data
Spring-cage connection
22.5 mm / 112 mm / 114.5 mm
Approx. 140 g
Spring-cage connection
0.2 mm² ... 1.5 mm²
AWG 24 ... 16
8 mm
-
-