Leuze electronic MSI 200 Series User Manual page 108

Configurable safety modules and safe extension modules
Table of Contents

Advertisement

Safe digital outputs IO0 to IO3 (if configured)
Limiting continuous current
Load
1
Capacitive
2
Inductive
Test pulses
Protective circuit
Short circuit protected
Status indicator
1
When using electromechanical components (e.g., contactors), the capacitive load can be disregarded.
2
Use a suitable and effective protective circuit on inductive loads.
Clock/signal outputs TM0 and TM1
Quantity
Type
Nominal voltage
Limiting continuous current
Test pulses
Short circuit protected
Times
Reaction time
Recovery time
General specifications
Nominal operating mode
Degree of protection in accordance with VDE 0470 part 1
Housing
Connection terminals
Installation location
Mounting type
Installation position
Housing material
Air and creepage distances between the circuits
Degree of contamination
Overvoltage category
Maximum power loss at rated conditions
Leuze electronic
4 x 0.5 A (see Derating)
Max. 1 μF (electronic components)
- (see protective circuit)
< 1 ms
Yes, within the scope of the operating voltage limits
Yes
4 x green LEDs
2
Digital
24 V DC (supply via A1/A2)
50 mA
~
1 ms
Yes
Max. 30 ms (plus reaction time MSI-EM200-4RO)
See appendix "Switch-off time of the MSI 100/200 system" on page 124.
< 10 s
100% ED
IP20
IP20
Min. IP54
DIN rail mounting
On horizontal DIN rail
Unreinforced polyamide PA, yellow
Acc. to EN 50178
2
III
2323 mW
(with f = 8, g = 2, h = 4, I
Clock
See appendix "Calculation of the power loss" on page 120
MSI 100/200
Technical data and ordering data
= 50 mA, I
= 500 mA)
Out/GND
108

Hide quick links:

Advertisement

Table of Contents
loading