ABB FSPS-21 User Manual page 96

Safety functions fieldbus module
Table of Contents

Advertisement

96 PROFINET IO – Communication protocol
Error #
Meaning
09h
No description data available
0Bh
No operation priority
0Fh
No text array available
11h
Request cannot be executed because of
operating mode
14h
Value impermissible
15h
Response too long
16h
Parameter address impermissible
17h
Illegal format
18h
Number of values inconsistent
65h ...
Manufacturer-specific error area
FF
65h
Vendor-specific error
66h
Request not supported
67h
Communication error
6Eh
Non-volatile error
6Fh
Time-out error
78h
PZD map failure
79h
PZD memory failure
7Ah
Multiple PZD map
82h
Control word bit map
8Ch
Set torque mode error
90h
Illegal Request ID
96h
Internal buffer
A0h
Internal communication
Used at
Access to an unavailable description (parameter value
is available)
Change access rights without rights to change para-
meters
Access to a text array that is not available (Parameter
value is available.)
Access is temporarily not possible for reasons that are
not specified in detail.
Change access with a value that is within limits but is
not permissible for other long-term reasons (parameter
with defined single values)
The length of the current response exceeds the max-
imum transmittable length.
Illegal value or value that is not supported for the attrib-
ute, number of elements, parameter number or sub-
index, or a combination
Write request: Illegal format or format of parameter
data that is not supported
Write request: Number of values of the parameter data
does not match the number of elements at the paramet-
er address.
Vendor-specific error
Request not supported
Request cannot be completed because of a communic-
ation error.
Failure during write to non-volatile memory
Request aborted because of a timeout.
Parameter cannot be mapped to PZD (size mismatch
or non-existent).
Parameter cannot be mapped to PZD (out of memory).
Parameter cannot be mapped to PZD (multiple PZD
write).
Cannot map Control word bit (parameter 933...937,
e.g., double mapping of bits).
Cannot change mode to TORQUE (frequency is used).
The request ID of the response is illegal.
Buffer overflow
Communication error between the module and the
drive

Hide quick links:

Advertisement

Table of Contents
loading