No.
Name/Value
15
Reserved
...
18
19
T16 scale
0...65535
20
Telegram type
0 = Unknown
3 = PPO3
4 = PPO4
6 = PPO6
7 = PPO7
8 = ST1
9 = ST2
21
Diagnostic alarm
0 = Enabled
1 = Disabled
22
Map selection
0 = 32bit
1 = 16bit
Description
These parameters are not used by the adapter module
when the module is configured for PROFINET IO.
Defines the scaling for reference 1 and actual 1 with
Transparent 16 profile. (Protocol.Profile = PNIO T16)
Scaling also depends on the selected Reference type
on 50.04 FBA A Ref 1 type and 50.34 FBA B Ref 1
type and 50.07 and 50.37 for the actual 1.
Ref type = Transparent
FBA_A/B_Ref1 = Ref1_from_PLC * (T16_Scale + 1)
Ref type = General
FBA_A/B_Ref1 = Ref1_from_PLC * (T16_Scale + 1)
/ 100
Reference multiplier/actual value divisor
Read-only. Indicates the telegram type selected for
PROFINET IO communication. The adapter module
automatically detects the telegram type defined in the
PLC.
For more information on the supported PPO message
types, see section
PPO types (page
Cyclical communication between the master and the
module has not been established yet.
PPO3 selected
PPO4 selected
PPO6 selected
PPO7 selected
ST1 selected
ST2 selected
Disables the PROFIdrive alarm mechanism which
generates alarms in case of drive faults.
But the standard PROFINET alarms are still sent.
For more information on the diagnostics and alarm
mechanism for PROFIdrive, see section
and alarm mechanism (page
PROFIdrive alarms are enabled.
PROFIdrive alarms are disabled.
Defines the preferred data type of mapped parameters
when mapping is done through PROFIdrive paramet-
ers.
Note:
Note: Supported with ACS580 and ACS880 drives
only.
32 bits
16 bits
PROFINET IO – Start-up 51
89).
Diagnostic
107).
Default
N/A
99
0 = Unknown
0 = Enabled
1 = 16bit