Event Messages; Leds - ABB FSPS-21 User Manual

Safety functions fieldbus module
Table of Contents

Advertisement

Code
Warning

Event messages

Code
Event
0xB795
FSx undefined event
0xB796
FSx diagnostics

LEDs

The adapter module is equipped with three bicolor diagnostic LEDs. The LEDs are described
below.
Description
Description
FSX undefined event.
If AUX = 0000 0000, no errors exist.
In any other case, gather the AUX codes from this event and contact
ABB.
AUX code(s)
What to do
0000 000A
Check PLC program
status.
PLC gave config
where fpar_crc does
If warning persists,
not match to calcu-
gather the AUX codes
lated one
from this fault and con-
tact ABB.
0000 0010
If warning persists,
gather the AUX codes
Received new f-
from this fault and con-
parameters
tact ABB.
0000 0011
Check PLC program
status.
Profisafe stack
stopped due to
If warning persists,
profinet state
gather the AUX codes
from this fault and con-
tact ABB.
0000 0012
Check PLC program
status.
Crc failure in cyclic
communication
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
0000 0013
Calculate a new watch-
dog time. See section
Watchdog timeout in
PROFIsafe response
cyclic communica-
time.
tion
0000 0014
If the warning reoccurs,
gather the AUX codes
PLC set bit4 (activ-
from this fault and con-
ate_fv) in cyclic
tact ABB.
communication
Fault tracing 183