ABB FSPS-21 User Manual page 172

Safety functions fieldbus module
Table of Contents

Advertisement

172 PROFIsafe
Fault
PROFIsafe communication watch-
dog time exceeds often.
All errors solved but you still cannot
start the PROFIsafe communication.
Cause
The watchdog time is too short.
After you have modified the config-
uration of the safety devices, you
may have to reboot of the whole
system before the changes take ef-
fect.
What to do
Calculate a new watchdog time. See
section
PROFIsafe response
time (page
122).
Reboot the safety PLC.
If this does not help, reboot also the
FSPS-21 module and the drive.
To reboot the FSPS-21 module:
• switch the power off and on, or
• use drive parameter FBA A/B
PAR REFRESH (parameter
51.27/54.27, see the drive firm-
ware manual).
To reboot the drive:
• switch the power off and on, or
• use drive parameter Control board
boot (parameter 96.08, see the
drive firmware manual).