130 PROFIsafe
11. Define the FSPS-21 properties:
•
Select FSPS_21.
•
On the General tab, define the IP address and Subnet mask, and type the Station
name (in this example, drive1).
Note:
Use only lower case letters for the Station name.
12. Return to the PROFINET controller (CM579-PNIO) properties. On the Assign IO-Device
name tab:
•
Click Connect to PLC (Login) and select the communication link used between
Control Builder and the PLC.
•
Click Scan to find all PROFINET devices connected to the network.
•
In the Configure station name box, select the station name defined for the module
in step 10 (in this example, drive1), and click Assign IO-Device name.
•
In the IP address and Network mask boxes, type the IP address and subnet mask
defined in step 11, and click Assign IP configuration.
13. Define the IO module properties:
•
Select the IO module PPO_Type_4.