130 PROFIsafe
11. Define the FSPS-21 properties:
Select FSPS_21.
On the General tab, define the IP address and Subnet mask, and type the Station
name (in this example, drive1).
Note:
Use only lower case letters for the Station name.
12. Return to the PROFINET controller (CM579-PNIO) properties. On the Assign IO-Device
name tab:
Click Connect to PLC (Login) and select the communication link used between
Control Builder and the PLC.
Click Scan to find all PROFINET devices connected to the network.
In the Configure station name box, select the station name defined for the module
in step 10 (in this example, drive1), and click Assign IO-Device name.
In the IP address and Network mask boxes, type the IP address and subnet mask
defined in step 11, and click Assign IP configuration.
13. Define the IO module properties:
Select the IO module PPO_Type_4.