ABB FSPS-21 User Manual page 102

Safety functions fieldbus module
Table of Contents

Advertisement

(multi-parameter)
In this example, the values 300 (12Ch) and 500 (1F4h) are written
to drive parameters 12.02 (0C.02h) and 20.08 (14.08h)
102 PROFINET IO – Communication protocol
respectively using one telegram.
Slot number
01 01 B0 2F 14 08 02 01 02 10 01 00 0C 00 02
DP
header
DP-V1 Command
Write_param_1202_2008_1.pdf
Subslot number
Index
Data length
Request reference
Request ID (02h= Change Parameter)
Drive object ID
Number of parameters
Attribute (10h = Value)
Number of elements
PROFIdrive V3 Parameter
Channel
•••
10 01 00 14 00 08
(Par. Channel cont'd)
42 01 01 2C
•••
(Par. Channel
42 01 01 F4
•••
(Par. Channel
Parameter number
Subindex
•••
•••
•••
cont'd)
DP
trailer
cont'd)
Value
Number of values
Format (42h = Word)