18. Set F-Parameters of the FSPS-21 module:
In the hardware configuration, double-click PROFIsafe ABB_PS3 to open the
Properties window.
On the PROFIsafe tab, modify the F_Dest_Add and F_WD_Time values as needed.
F_Source_Add is the address of the safety controller station. You can modify this
in the host F Parameters tab.
F_Dest_Add is the address of the FSPS-21 module. This is a control unit parameter
51.24, see section
two define the codename for the PROFIsafe relationship of this particular FSPS-21
module and the safety controller station.
Calculating the watchdog time (page 123)
F_WD_Time is the PROFIsafe watchdog time. See section
time (page 123)
Drive parameters related to safety functions (page
for instructions on how to calculate the correct watchdog time.
PROFIsafe 159
43). These
Calculating the watchdog