182 Fault tracing
Code
Warning
0xA7DD
FSx safety bus
warning
Description
PROFIsafe configura-
tion problem. Gather
the AUX codes from
this warning and con-
tact ABB.
AUX code(s)
What to do
0000 0001
Check the value of
parameter 51.24 F-des-
F_dest address does
tination address.
not match to con-
figured value
0000 0002
Check PLC program
status.
PLC gave illegal
f_dest address
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
0000 0003
Check PLC program
status.
F_source address
does not match to
If warning persists,
configured value
gather the AUX codes
from this fault and con-
tact ABB.
0000 0004
Check PLC program
status.
PLC gave illegal
f_source address
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
0000 0005
Check PLC program
status.
PLC gave illegal wd-
time value
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
0000 0006
Check PLC program
status.
PLC requested sil is
higher than we are
If warning persists,
capable
gather the AUX codes
from this fault and con-
tact ABB.
0000 0007
Check PLC program
status.
PLC gave config
which has conflict
If warning persists,
with f_crc_length
gather the AUX codes
from this fault and con-
tact ABB.
0000 0008
Check PLC program
status.
PLC gave config
which has conflict
If warning persists,
with f_par_version
gather the AUX codes
from this fault and con-
tact ABB.
0000 0009
Check PLC program
status.
PLC gave config
which has conflict
If warning persists,
with f_block_id
gather the AUX codes
from this fault and con-
tact ABB.

Hide quick links: