System Status Change From The Standalone Mode System Status - Siemens CPU 410-5H Process Automation System Manual

Simatic pcs 7 process control system
Table of Contents

Advertisement

Result:
The CPU displayed first in the table starts up as master CPU. Then the second CPU starts
up and will become the standby CPU after link-up and update operations.
Changing to standalone mode (starting only one CPU)
1. In the table, select the CPU you want to start up.
2. Select the
7.2.5

System status change from the standalone mode system status

Requirements:
● For CPU access protection with password: You have entered the CPU access password
● You have opened the "Operating state" dialog using the PLC > Operating state menu
● The standby CPU is not in ERROR-SEARCH operating state.
Changing to redundant system state (starting the standby CPU)
1. In the table, select the CPU that is in STOP, or the fault-tolerant system.
2. Select the Restart button (warm restart).
Changing to system status STOP (stopping the running CPU)
1. In the table, select the CPU that is in RUN, or the fault-tolerant system.
2. Select the Stop button.
Note
Any set up access right is not canceled until you stop the SIMATIC Manager. You should
reset the access right once again to prevent unauthorized access. You reset the access right
in the SIMATIC Manager with the menu command PLC > Access Rights > Cancel.
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA
Restart (warm restart)
with the menu command PLC > Access Rights > Setup in SIMATIC Manager.
command in SIMATIC Manager.
Operator controls and operating modes of the CPU 410-5H
7.2 System states of the redundant CPU 410-5H
button.
101