42 Start-up
FSCA-01 configuration parameters – group B (group 2)
Note: The actual parameter group number depends on the drive
type. Group B (group 2) corresponds to:
parameter group 55 in ACS355
parameter group 53 in ACSM1, ACS530, ACS850 and
ACQ810
parameter group 53 in ACS880 if the adapter is installed as
fieldbus adapter A or group 56 if the adapter is installed as
fieldbus adapter B
1)
No.
Name/Value
01
FBA data out1
(master to drive)
0 = None
101...9999
Other
02...
FBA data out2...
12
FBA data out12
1)
The number of parameters in this group may vary by drive type and drive firmware.
Description
Selects the drive parameter address into
which the value of the DATA OUT 1 register is
written (from the master to the server). The
Modbus register address maps are explained
in chapter
Communication
The content is defined by a decimal number in
the range of 0 to 9999 as follows:
0
Not used
1...99 Virtual address area of drive control.
Not used with Modbus/RTU.
101...
Parameter area of the drive
9999
Not used
Parameter index with format xxyy, where
xx is the parameter group number (1...99)
yy is the parameter number index within
that group (01...99).
Path to parameter area selection.
See parameter
01 FBA data
protocol.
out1.
Default
0 = None
0 = None