ABB FSCA-01 User Manual page 52

Rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

52 Start-up
Drive parameter
51.05 FBA PAR5
(PARITY)
51.06 FBA PAR6
(MODBUS TIMEOUT)
51.07 FBA PAR7
(TIMEOUT MODE)
52.01 FBA DATA IN1
52.03 FBA DATA IN3
53.01 FBA DATA OUT1
53.03 FBA DATA OUT3
51.27 FBA PAR REFRESH
10.01 EXT1 START FUNC
10.04 EXT2 START FUNC
24.01 SPEED REF1 SEL
32.01 TORQ REF1 SEL
34.01 EXT1/EXT2 SEL
34.03 EXT1 CTRL MODE1
Setting for ACSM1
drives
2)
0 (= 8 None 1)
2)
10
2)
2 (=Ctrl write)
2)
122
2)
107
2)
2408
2)
2410
REFRESH
FBA
FBA
FBA REF1
FBA REF2
P.FBA MAIN CW.15
Speed
Description
Defines the use of parity and
stop bit(s) and the data length.
Note: The parity setting of the
master has to be the same.
Sets the communication timeout
as 1 second.
The timeout feature monitors the
updating of the Control word and
Reference 1.
Power
DC bus voltage
Constant speed
Speed reference for jogging
function 1
Validates the FSCA-01
configuration parameter settings.
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 2.
Selects the fieldbus reference 1
as the source for speed
reference 1.
Selects the fieldbus reference 2
as the source for torque
reference 1.
Enables external control location
1/2 selection through the fieldbus
only (bit 15 in the fieldbus
Control word).
Selects speed control as the
control mode 1 for external
control location 1.