86 Diagnostics
Address
(4)00094
(4)00095
Error code
0x00
0x02
0x03
0x05
0x65
0x66
0x70
0x71
0x72
0x73
0x74
Registers (16-bit word)
Last register that was written successfully
Last register that was read successfully
Description
No error
Low or high limit
exceeded
Faulty subindex
Incorrect data type
General error in drive
communication
Timeout
Read-only
Parameter group
ended
MSB is not zero
LSB query start
MSB query end
Situation
Used when a Modbus query was
successful
Change access with a value
outside the value limits
Access to an unavailable
subindex of an array parameter
Change access with a value that
does not match the data type of
the parameter
Undefined error when handling a
Modbus query
Timeout in drive communication
when handling a Modbus query
An attempt to write a non-zero
value to a read-only drive
parameter
An attempt to write to multiple
parameter groups
An attempt to write a 16-bit
parameter with a 32-register
address and the MSB bytes are
not zero
An attempt to access only the
LSB register of the 32-bit
parameter
An attempt to access only the
MSB register of the 32-bit
parameter