ABB FSCA-01 User Manual page 64

Rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

64 Communication profiles
Bit
Name
7
ALARM
8
AT_
SETPOINT
9
REMOTE
10
ABOVE_
LIMIT
11
EXT_CTRL_
LOC
12
EXT_RUN_
ENABLE
13...
Drive-specific (For information, see the drive documentation.)
14
15
FBA_ERROR
Value
1
Warning/Alarm
0
No warning/alarm
1
OPERATION. Actual value equals reference
(= is within tolerance limits, ie, in speed
control, speed error is 10% max. of nominal
motor speed).
0
Actual value differs from reference (= is
outside tolerance limits.)
1
Drive control location: REMOTE (EXT1 or
EXT2)
0
Drive control location: LOCAL
1
Actual frequency or speed equals or exceeds
supervision limit (set by drive parameter).
Valid in both directions of rotation.
0
Actual frequency or speed within supervision
limit
1
External Control Location EXT2 selected.
Note concerning ACS880 and ACS860:
This bit is effective only if the fieldbus
interface is set as the target for this signal by
drive parameters. User bit 0 selection
(06.33).
0
External Control Location EXT1 selected
1
External Run Enable signal received.
Note concerning ACS880 and ACS860:
This bit is effective only if the fieldbus
interface is set as the target for this signal by
drive parameters. User bit 1 selection
(06.34).
0
No External Run Enable signal received
1
Communication error detected by fieldbus
adapter module
0
Fieldbus adapter communication OK
STATE/Description