Drive parameter
34.05 EXT2 CTRL MODE1
1) Read-only or automatically detected/set
2) Example
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 47Eh (1150 decimal) → READY TO SWITCH ON.
•
Enter 47Fh (1151 decimal) → OPERATING (Speed mode)
or
C7Fh (3199 decimal) → OPERATING (Torque mode).
Setting for ACSM1
drives
Torque
Start-up 53
Description
Selects torque control as the
control mode 1 for external
control location 2.