40 Start-up
No.
Name/Value
28
Par table ver
29
Drive type code
30
Mapping file ver
31
D2FBA comm sta
0 = Idle
1 = Exec.init
2 = Time out
3 = Conf.err
4 = Off-line
5 = On-line
6 = Reset
Description
Read-only. Displays the parameter table
revision of the fieldbus adapter module
mapping file stored in the memory of the
drive.
In format xyz, where
x = major revision number
y = minor revision number
z = correction number
OR
in format axyz, where
a = major revision number
xy = minor revision number
z = correction number or letter.
Parameter table revision
Read-only. Displays the drive type code of
the fieldbus adapter module mapping file
stored in the memory of the drive.
Drive type code of the fieldbus adapter
module mapping file
Read-only. Displays the fieldbus adapter
module mapping file revision stored in the
memory of the drive in decimal format.
Mapping file revision
Read-only. Displays the status of the
fieldbus adapter module communication.
Note: The value names may vary by drive.
Adapter is not configured.
Adapter is initializing.
A timeout has occurred in the
communication between the adapter and
the drive.
Adapter configuration error: The major or
minor revision code of the common
program revision in the fieldbus adapter
module is not the revision required by the
module or mapping file upload has failed
more than three times.
Adapter is off-line.
Adapter is on-line.
Adapter is performing a hardware reset.
Default
N/A
N/A
N/A
0 = Idle
OR
4 = Off-line