ABB FSCA-01 User Manual page 39

Rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

No.
Name/Value
13...
Reserved
23
24
Protocol check
0...5
25
Protocol
0
1 = Modbus
2 = N2
3 = FLN
4 = BACnet
5 = DCP
26
Protocol sw ver
27
FBA par refresh
0 = Done
1 = Refresh /
Configure
Description
These parameters are not used by the
adapter module.
Read only. Shows whether the parameters
of the selected communication protocol
have been loaded to the module.
- If the value of this parameter corresponds
to the setting of par.
25
that the parameters have been loaded.
- If the value of this parameter differs from
the setting of par. 25, load the parameters
by setting par.
27 FBA par refresh
Refresh / Configure.
Communication protocol check
Selects the communication protocol for the
network connection.
No protocol selected
Modbus/RTU protocol selected
N/A
N/A
N/A
N/A
Read only. Shows the software version of
the communication protocol currently
selected.
Version of the communication protocol
Validates any changed adapter module
configuration parameter settings. After
refreshing, the value reverts automatically
to 0 = Done.
Note: This parameter cannot be changed
while the drive is running.
Refreshing done
Refreshing
Protocol, it means
to 1 =
Start-up 39
Default
N/A
1
1 = Modbus
N/A
0 = Done