48 Start-up
Drive parameter
1102 EXT1/EXT2 SEL
1103 REF1 SELECT
1106 REF2 SELECT
1601 RUN ENABLE
1604 FAULT RESET SEL
1) Read-only or automatically detected/set
2) Example
The start sequence for the parameter example above is given
below.
Control word:
Reset the fieldbus communication fault (if active).
Enter 47Eh (1150 decimal) → READY TO SWITCH ON.
Enter 47Fh (1151 decimal) → OPERATING (Speed mode)
or
C7Fh (3199 decimal) → OPERATING (Torque mode).
Setting for
ACS355 drives
8 = COMM
8 = COMM
8 = COMM
7 = COMM
8 = COMM
Description
Enables external control location
1/2 selection through the fieldbus.
Selects the fieldbus reference 1 as
the source for speed reference.
Selects the fieldbus reference 2 as
the source for torque reference.
Selects the fieldbus interface as
the source for the inverted Run
enable signal (Run disable).
Selects the fieldbus interface as
the source for the fault reset
signal.