Note 2: With 32-bit parameters, one can only assign process
data to every second configuration parameter (eg, 52.01,
52.03, 52.05, and so on).
8. Save the valid parameter values to permanent memory by
setting parameter 96.07 Parameter save to Save.
9. Validate the settings made in parameter groups 51, 52 and 53
by setting parameter 51.27 FBA par refresh to Configure.
10. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
Parameter setting examples – ACS880
Speed control using the ABB Drives - Enhanced
communication profile
This example shows how to configure a speed control application
that uses the ABB Drives - Enhanced profile.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see the state machine on
page 65.
When Reference 1 (REF1) is used, a reference value of ±20000
(4E20h) corresponds to the reference set with parameter 46.01
Speed scaling in the forward and reverse directions.
Start-up 55