ABB FSCA-01 User Manual page 37

Rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

No.
Name/Value
08
OK messages
0...65535
09
CRC errors
0...65535
10
UART errors
0...65535
11
Word order
0 = LOHI
1 = HILO
12
Address mode
Description
Read-only. Shows the number of valid
messages which the drive has received.
Number of valid messages
Read-only. Shows the number of
messages with a cyclic redundancy check
(CRC) error which the drive has received.
If the number is high, check the CRC
calculation for possible errors.
Note: High electromagnetic noise levels
may generate errors.
Number of messages with a CRC error
Read-only. Shows the number of
messages which the drive has received
with other communication errors.
Number of messages with other
communication errors
Selects in which order the 16-bit registers
of 32-bit parameters are transferred.
For each register (16-bit), the first byte
contains the high order byte and the last
byte contains the low order byte. The
covers holding register range of 1...65535.
The first register contains the low order
word and the second register contains the
high order word.
The first register contains the high order
word and the second register contains the
low order word.
Defines the mapping between parameters
and holding registers in the 0...65535
Modbus register range.
Start-up 37
Default
0
0
0
1 = HILO
0 =
Mode 0