Starting up ACS355 drives

1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter 9802 COMM PROT SEL to EXT
FBA.
3. Set the FSCA-01 configuration parameters in group 51.
Select the communication protocol with parameter 5125
and profile with parameter 5102.
Configure the network settings with parameters
5103...5105.
With parameters 5106 and 5107, select how the adapter
module detects fieldbus communication breaks.
4. With parameter 3018 COMM FAULT FUNC, select how the
drive reacts to a fieldbus communication break.
5. With parameter 3019 COMM FAULT TIME, define the time
between communication break detection and the selected
action.
6. Define the process data transferred to and from the drive in the
FSCA-01 configuration parameter groups 54 and 55.
Note: The adapter module assigns the Control word, Status
word, references 1...2 and actual values 1...2 automatically to
Modbus registers. Process data groups are not available for
the ABB Drives - Classic communication profile.
7. Validate the settings made in parameter groups 51, 54 and 55
by setting parameter 5127 FBA PAR REFRESH to REFRESH.
8. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
Start-up 45