ABB FSCA-01 User Manual page 47

Rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

Drive parameter
5102 FB PAR 2
(PROFILE)
5103 FB PAR 3
(STATION ID)
5104 FB PAR 4
(BAUD RATE)
5105 FB PAR 5
(PARITY)
5106 FB PAR 6
(MODBUS TIMEOUT)
5107 FB PAR 7
(TIMEOUT MODE)
3018 COMM FAULT FUNC
3019 COMM FAULT TIME
5401 FBA DATA IN 1
5402 FBA DATA IN 2
5501 FBA DATA OUT 1
5502 FBA DATA OUT 2
5127 FBA PAR REFRESH
9904 MOTOR CTRL
MODE
1001 EXT1 COMMANDS
1002 EXT2 COMMANDS
Setting for
ACS355 drives
1 (= ABB
Enhanced)
2)
3
2)
4 (= 115.2 kbit/s)
2)
0 (= 8 None 1)
2)
10
2)
2 (=Ctrl write)
2)
1 = FAULT
2)
3.0 s
2)
106
2)
107
2)
1202
2)
1203
1 = REFRESH
2 = VECTOR:
TORQ
10 = COMM
10 = COMM
Description
Selects the ABB Drives -
Enhanced profile.
Defines the address of the device.
Selects the baud rate of the link.
Note: The baud rate of the master
has to be the same.
Defines the use of parity and stop
bit(s) and the data length.
Note: The parity setting of the
master has to be the same.
Sets the communication timeout
as 1 second.
The timeout feature monitors the
updating of the Control word and
Reference 1.
Enables fieldbus communication
fault monitoring.
Defines the fieldbus
communication break supervision
time.
Power
DC bus voltage
Constant speed 1
Constant speed 2
Validates the FSCA-01
configuration parameter settings.
Selects the vector control mode as
the motor control mode.
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 2.
Start-up 47