Installation
Relay 9/J71. Dead closing function (230V/400V machine)
To use the closing function without a power supply, follow these instructions:
•
Remove the blue 0.75mm² wire from connector N1 or N2 in the electrical
cabinet to contact J71-102.
•
Remove the black 0.75mm² wire from connector X10 contact J71-105.
•
Connect the equipment to be controlled to contacts J71-101 and J71-105.
Relay 9/J71. Relay 9. 24V AC version
(230V/400V 3-phase machine)
To connect a 24V AC power supply to the contact, follow these instructions:
•
Remove the blue 0.75mm² wire from connector N1 or N2 in the electrical
cabinet to contact J71-102.
•
Remove the black 0.75mm² wire from connector X10 contact J71-105.
•
Connect a red 0.75mm² wire from connector 0V in the electrical cabinet to
contact J71-102.
•
Connect a red 0.75mm² wire from the 8-pin contact on the data card la-
belled J69-8 (24V) to contact J71-105.
•
Connect the equipment to be controlled to contacts J71-101 and J71-102.
There will be two wires connected to contact J71-102.