AC300 Series Vector Control Inverter Manual
F11.22

PID output upper limit

Setting range: 0.0-100.0%
F11.23

PID output lower limit

Setting range: -100.0-F11.19
F11.24

PID output filter time

Setting range: 0.000-6.000s
[F11.22 ] is used to set the PID output upper limit;[F11.23] sets the PID output lower limit.
[F11.24] PID output filter time used to filter the PID output.It will weak the surge caused by PID output result, and
decrease the closed-loop system response performance.
F11.25
Detection time while feedback wire break
F11.26
Act selections while feedback wire break
F11.27
Wire break alarm upper limit
F11.28
Wire break alarm lowest limit
While PID given frequency and inverter is running, if feedback signal which is bigger the [F11.27] or smaller than
[F11.28] is detected out and keeps for [F11.25] delay time, it is considered as sensor wire break.
Feedback wire-break action selections
0: Go on PID operation without alarm: no wire-break detection when invalid
1: Stop and alarm malfunction: When the inverter detects a sensor break, immediately block output, motor free
stop and report E.PID fault.
2: Go on PID operation and output alarm signal: When the inverter detects a sensor break, still run by the PID
regulation, but the keyboard displays E.PID fault and flashes.
3: Run the current frequency and output alarm signal: When the inverter detects a sensor break, maintain
constant output frequency before the fault, but the keyboard displays E.PID fault and flashes.
Wire break alarm upper limit:
Set the upper limit of PID sensor wire break detection.When feedback signal is over alarm upper limit for time
[F11.25], it is considered as sensor wire break.
Wire break alarm lower limit:
Set the lower limit of PID sensor wire break detection.When feedback signal is under alarm upper limit for time
[F11.25], it is considered as sensor wire break.
F11.29
Constant pressure water supply sleep selection
F11.30
Sleep frequency
F11.31
Sleep delay
F11.32
Wake-up deviation
F11.33
Wake-up delay
Constant pressure water supply sleep selection:
Function Parameter Specifications
Factory set: 100.0%
Factory set: 0.0%
Factory set: 0.0s
Setting range: 0.0-120.0s
Factory set: 1.0s
Setting range: 0-3
Factory set: 0
Setting range: 0.0-100.0%
Factory set: 100.0%
Setting range: 0.0-100.0%
Factory set: 0.0%
0: Invalid 1: Valid
Factory default: 0
0.00Hz ~ max frequency F0.09
Default: 10.00
0.0~3600.0 s
Default: 60.0
0.0~50.0%
Default: 5.0
0.0~60.0S
Default: 1.0
136
AC300 Series Vector Control Inverter Manual
0: Invalid no sleep detection
1: Valid
for sleep detection
Sleep into the judgment:
When the constant pressure water supply sleep function is valid, when the PID adjustment output frequency is lower
than the set [F11.30] sleep frequency, it will enter the sleep state after the [F11.31] sleep delay (ie, the output will be
blocked after deceleration to zero frequency).
Sleep wakeup judgment:
When the PID feedback characteristic is positive:
The PID reference (C00.08) minus the wake-up deviation (F11.32) is compared with the PID feedback (C00.09). If it
continues to be greater than the wake-up delay [F11.33], it exits the sleep state and enters the normal operating status.
When the PID feedback characteristic is inverse characteristic:
The PID reference (C00.08) plus the wake-up deviation (F11.32) is compared with the PID feedback (C00.09). If it
continues to be greater than the wake-up delay [F11.33, exit the sleep state and enter the normal running state.

8.12 Multistep, PLC Function and Swing Frequency Parameters

F12.00
Step 1
Setting range: 0.00-max frequency
F12.01
Step 2
Setting range: 0.00-max frequency
F12.02
Step 3
Setting range: 0.00-max frequency
F12.03
Step 4
Setting range: 0.00-max frequency
F12.04
Step 5
Setting range: 0.00-max frequency
F12.05
Step 6
Setting range: 0.00-max frequency
F12.06
Step 7
Setting range: 0.00-max frequency
F12.07
Step 8
Setting range: 0.00-max frequency
F12.08
Step 9
Setting range: 0.00-max frequency
F12.09
Step 10
Setting range: 0.00-max frequency
F12.10
Step 11
Setting range: 0.00-max frequency
F12.11
Step 12
Setting range: 0.00-max frequency
F12.12
Step 13
Setting range: 0.00-max frequency
F12.13
Step 14
Setting range: 0.00-max frequency
F12.14
Step 15
Setting range: 0.00-max frequency
It sets run frequency of 15 steps in PLC and multistep control.
Mult steps control has priorty only after JOG. While multi steps control, 4 multifunction input terminals are needed to
set as control terminals. Set details refer to [F02.00-F02.06].
Inverter is running at which step is decides by the ON/OFF state of 4 control terminal and COM. Run and direction is
controlled by run signal and direction gived by [F0.02]. ACC/DEC time default is ACC/DEC time 1 [F0.14], [F0.15]. Or
select ACC/DEC time by ACC/DEC time selection terminal set by [F02.00-F02.06].
Function Parameter Specifications
Factory set: 10.00Hz
Factory set: 20.00 Hz
Factory set: 30.00 Hz
Factory set: 40.00 Hz
Factory set: 50.00 Hz
Factory set: 40.00 Hz
Factory set: 30.00 Hz
Factory set: 20.00 Hz
Factory set: 10.00 Hz
Factory set: 20.00 Hz
Factory set: 30.00 Hz
Factory set: 40.00 Hz
Factory set: 50.00 Hz
Factory set: 40.00 Hz
Factory set: 30.00 Hz
137