AC300 Series Vector Control Inverter Manual
LED"0" digit: Feedback feature
selection
0: Positive feature
feature
F11.07
PID control selection
LED"00"/"000" digit: Reserved
LED"0000" digit: Differential
adjustment properties
0: Differential bias
1: Differential of feedback
F11.08
PID preset output
0.0~100.0%
PID preset output
F11.09
0.0~6500.0s
running time
PID control deviation
F11.10
0.0~100.0%
F11.11
Proportional gain P1
0.000~8.000
F11.12
Integral time I1
0.0~600.0s
F11.13
Differential time D1
0.000~6.000s
F11.14
Proportional gain P2
0.000~8.000
F11.15
Integral time I2
0.0~600.0s
F11.16
Differential gain D2
0.000~6.000s
0: No switch
PID Parameter
F11.17
1: Use DI terminal to switch
switching condition
2: Switch according to deviation
Low value of
F11.18
0.0~100.0%
switching deviation
High value of
F11.19
0.0~100.0%
switching deviation
F11.20
Reserved
F11.21
Differential limit
0.0~100.0%
F11.22
PID output upper limit
0.0~100.0%
F11.23
PID output lower limit
-100.0~F11.19
F11.24
PID output filter time
0.000~6.000s
Feedback wire break
F11.25
0.0~120.0s
detection time
0: Go on PID operation without alarm
1: Stop and alarm malfunction
Feedback wire break
2: continue to PID operation and
F11.26
action selection
output alarm signal
3: Run at the current frequency and
output alarm signal
Wire break alarm
F11.27
0.0~100.0%
F11.28
Wire break alarm
0.0~100.0%
Close-loop suspend
F11.29
0.0~100.0%
detection threshold
Close-loop suspend
F11.30
0.0~600.0s
detection time
Function Parameter Table
1:Negative
0100
●
0xB07
100.0%
●
0xB08
0.0s
●
0xB09
0.0%
●
0xB0A
0.100
●
0xB0B
1.0s
●
0xB0C
0.000s
●
0xB0D
0.100
●
0xB0E
1.0s
●
0xB0F
0.000s
●
0xB10
0
●
0xB11
20.0%
●
0xB12
80.0%
●
0xB13
0xB14
5.0%
●
0xB15
100.0%
●
0xB16
0.0%
●
0xB17
0.000s
●
0xB18
1.0s
●
0xB19
0
●
0xB1A
100.0%
●
0xB1B
0.0%
●
0xB1C
0.0%
●
0xB1D
1.0s
●
0xB1E
170
AC300 Series Vector Control Inverter Manual
Multi-Speed and PLC Function Parameter Group
NO.
Function description
Range of setting and definition
F12.00
PLC Speed 1
0.00~Max frequency
F12.01
PLC Speed 2
0.00~Max frequency
F12.02
PLC Speed 3
0.00~Max frequency
F12.03
PLC Speed 4
0.00~Max frequency
F12.04
PLC Speed 5
0.00~Max frequency
F12.05
PLC Speed 6
0.00~Max frequency
F12.06
PLC Speed 7
0.00~Max frequency
F12.23
PLC Speed 8
0.00~Max frequency
F12.08
PLC Speed 9
0.00~Max frequency
F12.09
PLC Speed 10
0.00~Max frequency
F12.10
PLC Speed 11
0.00~Max frequency
F12.11
PLC Speed 12
0.00~Max frequency
F12.12
PLC Speed 13
0.00~Max frequency
F12.13
PLC Speed 14
0.00~Max frequency
F12.14
PLC Speed 15
0.00~Max frequency
LED"0" digit: cycle mode
0: Stop after single cycle
1: Continuous cycles
2: Keep final value after single cycle
LED"00" digit: Time unit
0: second
2:hour
PLC Running mode
F12.15
LED"000" digit: Power down
selection
memory
0: Not save
LED"0000" digit: Start mode
0: Restart from the 1st stage
1: Restart from the stop stage
2: Continue running from the time
when stop
PLC 1st step running
F12.16
0.0~6500.0(s/m/h)
F12.17
PLC 2nd step running
0.0~6500.0(s/m/h)
F12.18
PLC 3rd step running
0.0~6500.0(s/m/h)
F12.19
PLC 4thstep running time
0.0~6500.0(s/m/h)
F12.20
PLC 5th step running
0.0~6500.0(s/m/h)
F12.21
PLC 6th step running
0.0~6500.0(s/m/h)
PLC 7th step running
F12.22
0.0~6500.0(s/m/h)
F12.23
PLC 8th step running
0.0~6500.0(s/m/h)
PLC 9th step running
F12.24
0.0~6500.0(s/m/h)
F12.25
PLC 10th step running
0.0~6500.0(s/m/h)
F12.26
PLC 11th step running
0.0~6500.0(s/m/h)
Function Parameter Table
Factory
Feature
Address
default
10.00Hz
●
0xC00
20.00Hz
●
0xC01
30.00Hz
●
0xC02
40.00Hz
●
0xC03
50.00Hz
●
0xC04
40.00Hz
●
0xC05
30.00Hz
●
0xC06
20.00Hz
●
0xC07
10.00Hz
●
0xC08
20.00Hz
●
0xC09
30.00Hz
●
0xC0A
40.00Hz
●
0xC0B
50.00Hz
●
0xC0C
40.00Hz
●
0xC0D
30.00Hz
●
0xC0E
1: minute
0000
●
0xC0F
1: save
10.0
●
0xC10
10.0
●
0xC11
10.0
●
0xC12
10.0
●
0xC13
10.0
●
0xC14
10.0
●
0xC15
10.0
●
0xC16
10.0
●
0xC17
10.0
●
0xC18
10.0
●
0xC19
10.0
●
0xC1A
171