AC300 Series Vector Control Inverter Manual
LED"0" digit: Detection
selection(protection 1)
0: Not detection
1: Detected load is too large
2: Detected load is too large only at
constant speed
3: Detected underloaded
4: Detected underloaded only at
constant speed
LED"00" digit: Alarm selection
0: alarm and continue operation
Load pre alarm
F10.17
1: Fault protection and free stop
detection setting
LED"000" digit: Detection
selection
(protection 2)
0: Not detection
1: Detected load is too large
2: Detected load is too large only at
constant speed
3: Detected underloaded
4: Detected underloaded only at
constant speed
Pre alarm detection
F10.18
0.0~200.0%
level 1 for load
Load pre alarm
F10.19
0.0~60.0s
detection time 1
Pre alarm detection
F10.20
.0~200.0%
level 2 for load
Load pre alarm
F10.21
0.0~60.0s
detection time 2
F10.22
Reserved
LED "0" digit: Detection selection
0: Not detected
1: Detected only at constant speed
Protection action of
2: Detecting
F10.23
speed bias excess
LED "00" digit: Alarm selection
0: Free stop and report fault
1: Alarm and continue operation
LED "000"/"0000" digit: Reserved
Detection threshold
F10.24
0.0~60.0%
when speed bias
Detection time when
F10.25
0.0~60.0s
speed bias excess
Function Parameter Table
0000
0xA11
130.0%
0xA12
5.0s
0xA13
30.0%
0xA14
5.0s
0xA15
0xA16
0000
0xA17
10.0%
0xA18
2.0s
0xA19
168
AC300 Series Vector Control Inverter Manual
LED "0" digit: Detection selection
0: Not detected
1: Detected at constant speed
2: Detecting
F10.26
Stall protection action
LED "00" digit: Alarm selection
0: Free stop and report fault
1: Alarm and continue operation
LED "000" digit: Reserved
LED "0000" digit: Reserved
Stall detection
F10.27
0.0~150.0%
F10.28
Stall detection time
0.000~2.000s
Motor overshot
F10.29
0~200°C
Protection threshold
Motor overshot Pre
F10.30
0~200°C
alarm threshold
F10.31-F
Reserved
10.37
Malfunction
F10.38
0~5
self-recovery times
Malfunction
F10.39
0.1~100.0s
self-recovery interval
PID Process Control Parameter Group
NO.
Function description
Range of settings and definition
0: Keypad digit PID
given
PID Controller given
1: Reserved
F11.00
signal source
2: AI1
3: AI2
4: Reserved
Keyboard digit PID
F11.01
0.00~100.0%
given / feedback
F11.02
PID given changing
0.00~60.00s
0: Keypad digital
PID feedback
PID controller
1: Reserved
F11.03
feedback signal
2: AI1
source
3:AI2
F11.04
Feedback signal filter
0.000~6.000s
F11.05
Feedback signal gain
0.00~10.00
F11.06
Given and feedback
0~100.0
Function Parameter Table
0000
0xA1A
110.0%
0xA1B
0.010s
0xA1C
0xA1D
0xA1E
0
0xA26
1.0s
0xA27
Factory
Feature
Address
default
5: PUL
6: RS485
7:
Option
0
0xB00
card
8:Terminal
selection
50.0%
0xB01
1.00s
0xB02
4: Reserved
5: PUL
6: RS485
7:
Option
2
0xB03
card
8:Terminal
selection
0.010s
0xB04
1.00
0xB05
100.0
0xB06
169