Malfunction And Protection Parameters; Surge Suppression Gain; Auto Energy Save Selection; Energy Saving Frequency Lower Limit - Veichi AC300 Series Technical Manual

Hide thumbs Also See for AC300 Series:
Table of Contents

Advertisement

AC300 Series Vector Control Inverter Manual
Output
Voltage
Motor rated
voltage
Torque
boost
Output
voltage
frequency
0
Torque boost cut-
Motor rated
off frequency
frequency
Torque lifting diagram
F08.14
slip compensation gain
Setting range:0.0-200.0%
F08.15
Slip compensation limit
Setting range:0.0-300.0%
F08.16
Slip compensation filter time
Setting range:0.000-6.000s
It makes inverter output frequency self adjust within a setting range according motor load change to compensate slip
frequency to make motor keep constant speed. It effectively relieves the impact of load change to motor speed.
Slip compensation diagram
If it is used with the automatic torque boost function,the low frequency trait can be promoted obviously.100.0% slip
frequency compensation corresponds to the motor rated slip; it may cause the motor speed exceeds setting value when
the compensation value is set too large .Hence, [F08.15] setting need to be limited.Slip compensation filter time is to
filter the slip compensation to eliminate disturb signal. The longer filter time is, the stronger anti-disturb force is. The
shorter filter time is, the weaker anti-disturb force is. But respond speed will be quicker.
The slip compensation function needs to correctly input the motor nameplate parameters and learn the
parameters to achieve the best results.
F08.17

Surge suppression gain

Setting range: 0.0-900.0%
While the motor control mode F0.00=0 or 1,it is easily to appear motor current instability and motor speed oscillation
Function Parameter Specifications
Output
Voltage
Motor rated
voltage
Torque
boost
Output
voltage
frequency
0
Torque boost cut-
Motor rated
off frequency
frequency
Factory set:100.0%
Factory set:100.0%
Factory set:0.200s
Factory set: 100.0%
122
AC300 Series Vector Control Inverter Manual
phenomenon in medium and high power occasions , which is a combination of electrical and mechanical effects of
low-frequency resonance. It is possible to suppress the low frequency resonance by adjusting the [F08.17], but
excessive suppression gain may lead to additional stability problems.
F08.18
Reserved
F08.19
Auto energy saving control
Setting range: 0-1
F08.20

Energy saving frequency lower limit

Setting range: 0.0-50.0Hz
F08.21
Energy saving voltage lower limit
Setting range: 0.0-100.0%
F08.22
Energy saving voltage regulation rate
Setting range: 0~0.200V/MS
F08.23
Energy saving voltage recovery rate
Setting range: 0~0.200V/MS

Auto energy save selection:

Under the condition of light load, the motor can adjust the output voltage automatically after entering the constant
speed to promote the efficiency to save energy.
0: OFF
1: ON
Energy saving frequency lower limit:
When output frequency is lower than this value, auto energy save function will exit.
Energy saving voltage lower limit:While automatically saving energy running,the lower limit of the voltage can
reduce.100.0% is corresponding to the current output voltage corresponding to the output frequency without saving
energy.
Energy saving voltage regulation rate:
The rate of voltage regulation during the process of energy saving.
Energy saving voltage recovery rate:
The rate of voltage recovery to the normal voltage while exit the energy saving process.
Note: Enter energy saving only at constant speed running, hence this function is not suitable to be used in
occasions where the given frequency changes frequently.
F08.24~F08.34
Reserved

8.10 Malfunction and Protection Parameters

F10.00
OC suppression function
Setting range: 0~1
F10.01
OC suppression point
Setting range: 0.0-300.0%
F10.02
OC suppression gain
Setting range: 0.0-500.0%
Function Parameter Specifications
Factory set: 0
Factory set: 15.00Hz
Factory set: 50.0%
Factory set:0.010V/MS
Factory set:0.200V/MS
Factory default: 0
Factory default: 160.0%
Factory default: 100.0%
123

Advertisement

Table of Contents
loading

Table of Contents