AC300 Series Vector Control Inverter Manual
F12.27
PLC 12th step running
0.0~6500.0(s/m/h)
F12.28
PLC 13th step running
0.0~6500.0(s/m/h)
PLC 14th step running
F12.29
0.0~6500.0(s/m/h)
F12.30
PLC 15th step running
0.0~6500.0(s/m/h)
F12.31
F12.32
F12.33
LED"0" digit: current step run
F12.34
direction
0: FWD
F12.35
1: REV
F12.36
LED"00" digit: ACC/DEC time in
F12.37
PLC 1st-15th step
this step
F12.38
direction and ADD/DEC
0: ACC/DEC time 1
time
F12.39
1: ACC/DEC time 2
F12.40
2: ACC/DEC time 3
F12.41
3: ACC/DEC time 4
F12.42
LED"000" digit: Reserved
LED"0000" digit: Reserved
F12.43
F12.44
F12.45
F12.46
Reserved
-
F12.49
Swing frequency control
0: invalid
Swing frequency
0: Relative to central frequency
F12.50
amplitude
1: Relative to max frequency
F12.51
Reserved
0.0~100.0%
F12.52
Swing frequency
Jump frequency
F12.53
0.0~50.0%
lit d
Swing frequency rising
F12.54
0.00~650.00s
F12.55
Swing frequency falling
0.00~650.00s
Communication Control Function Parameter Group
NO.
Function description
Range of setting and definition
LED "0" digit: Modbus
main-slave selection
F13.0
Main-slave machine
0: Slave machine
0
selection
1: Main machine
F13.0
485 communication
1~247
LED"0" digit:485 communication
0:1200 bps
F13.0
Communication baud rate
2:4800 bps
2
selection
4:19200 bps
LED "00" /"000"/"0000"digit:
reserved
Function Parameter Table
10.0
0xC1B
10.0
0xC1C
10.0
0xC1D
10.0
0xC1E
0000
0xC1F
0000
0xC20
0000
0xC21
0000
0xC22
0000
0xC23
0000
0xC24
0000
0xC25
0000
0xC26
0000
0xC27
0000
0xC28
0000
0xC29
0000
0xC2A
0000
0xC2B
0000
0xC2C
0000
0xC2D
1: valid
0
0xC31
0
0xC32
10.0%
0xC34
10.0%
5.00s
0xC36
5.00s
0xC37
Factory
Feature
Address
default
0000
0xD00
1
0xD01
1:2400 bps
3:9600 bps
0003
0xD02
5:38400 bps
172
AC300 Series Vector Control Inverter Manual
0:
F13.0
(N,8,1)format
Modbus data format
3
1: (E,8,1)
f
F13.0
Communication ratio
0.00~5.00
F13.0
Modbus communication
0~500ms
5
answer delay
F13.0
Modbus communication
0.1~100.0s
6
overtime fault time
0: No checked overtime fault
Modbus communication
F13.0
1: alarm and stop freely
fault action mode
7
2: Alarm and continue running
selection
3: Forced stop
F13.0
Modbus Responds
0:Write operation with response
8
dispose
1: Write operation without response
LED"0"digit: the first group
transmitting frame selection
0: Invalid
1: Main machine run command
2: Main machine given frequency
3: Main machine output frequency
4: Main machine upper limit
frequency
5: Main machine given torque
6: Main machine output torque
F13.0
Main machine sending
7/8: Reserved
9
selection
9: Main machine given PID
A: Main machine feedback PID
LED"00"digit: the second group
transmitting frame selection
LED"000"digit:
the third group transmitting
frame selection
LED"0000"digit: the fourth group
transmitting frame selection
Same as above
F13.1
RS485 Communication
0: Modbus communication
0
port configuration
1: serial port communication
Terminal of Input and Output Function Selection
X
Function Specification
X
Function Specification
16-1
0
No function
Multispeed terminal 1-4
1
FWD
20
PID control cancel
2
REV
21
PID control pause
3
3-line running(Xi)
22
PID trait switch
4
FWD JOG
23
PID gain switch
Function Parameter Table
3: (N,8,2) format
4: (E,8,2) format
0
0xD03
5: (O,8,2)
f
1.00
0xD04
0ms
0xD05
1.0s
0xD06
0
0xD07
0
0xD08
0031
0xD09
0
0xD0A
X
Function
41
Timer clear terminal
42
Counter input
43
Counter clear
DC braking
44
45
Pre excitation
173