Control Loop Terminals; Control Loop Terminals Array - Veichi AC300 Series Technical Manual

Hide thumbs Also See for AC300 Series:
Table of Contents

Advertisement

AC300 Series Vector Control Inverter Manual
AC300-T3-5R5G
25A
20A
AC300-T3-7R5G
25A
30A
AC300-T3-011G
32A
40A
AC300-T3-015G
40A
50A
AC300-T3-018G
50A
60A
AC300-T3-022G
50A
75A
AC300-T3-030G
63A
100A
AC300-T3-037G
80A
125A
AC300-T3-045G
100A
150A
AC300-T3-055G
125A
175A
AC300-T3-075G
160A
200A
AC300-T3-090G
220A
250A
AC300-T3-110G
220A
300A
AC300-T3-132G
250A
400A
AC300-T3-160G
300A
500A
AC300-T3-185G
400A
600A
AC300-T3-200G
400A
700A
AC300-T3-220G
630A
800A
AC300-T3-250G
630A
1000A
AC300-T3-280G
630A
1200A
AC300-T3-315G
630A
1200A
AC300-T3-355G
800A
1400A
AC300-T3-400G
1000A
1600A
AC300-T3-450G
1000A
2000A
AC300-T3-500G
1000A
2000A
AC300-T3-560G
------
2000A
Note: For DC reactor, input filter, output filter and other components specification details and circuit mode, please
refer chapter 7 "peripheral equipments and options"
Installation and Wiring
------
NFI-020
NFO-020
------
NFI-020
NFO-020
------
NFI-036
NFO-036
------
NFI-036
NFO-036
------
NFI-050
NFO-050
------
NFI-050
NFO-050
DCL-80
NFI-080
NFO-080
DCL-100
NFI-100
NFO-100
DCL-110
NFI-100
NFO-100
DCL-125
NFI-150
NFO-150
DCL-150
NFI-150
NFO-150
DCL-200
NFI-200
NFO-300
DCL-200
NFI-200
NFO-300
DCL-300
NFI-300
NFO-300
DCL-300
NFI-300
NFO-300
DCL-400
NFI-400
NFO-400
DCL-400
NFI-400
NFO-400
DCL-500
NFI-600
NFO-600
DCL-600
NFI-600
NFO-600
DCL-600
NFI-600
NFO-600
DCL-800
------
------
DCL-800
------
------
DCL-1000
------
------
DCL-1000
------
------
DCL-1200
------
------
DCL-1200
------
------
24
AC300 Series Vector Control Inverter Manual

Control loop terminals

● Control loop terminals array
Table 3-7:AC300 series inverter control loop terminals array and definition
Sort
Terminal
Name
+10V-GND
External +10V power supply
+24V-COM
External +24V power supply
Power
supply
External
PLC
common terminal
AI1-GND
Voltage or current type analog input
Analog input
AI2-GND
Voltage or current type analog input
Digital input
X1-PLC
Multi-function contact input 1
Installation and Wiring
Function definition
Provide +10V power supply to the outside,
the maximum output current: 50 mA is
generally used as external potentiometer
working power supply, potentiometer
resistance range: 1KΩ ~ 5KΩ
Provides +24V power supply to the
outside, generally used as digital input
and output terminal working power supply
and external sensor power supply
Maximum output current: 100 mA
Factory default connection with +24V
When using X1~X5/PUL to drive the
external signal, the PLC needs to be
connected to the external power supply
and disconnected from the +24V power
supply (see "+24V", "PLC", "COM"
connection diagram for details)
1. Input current range: DC 0V ~ 10V / 0mA
~ 20mA
2. Voltage type input impedance: 100KΩ
3. Current input impedance: 500Ω
1. Input current range: DC 0V ~ 10V / 0mA
~ 20mA
2. Voltage type input impedance: 100KΩ
3. Current input impedance: 500Ω
Optocoupler isolation, compatible with
25

Advertisement

Table of Contents
loading

Table of Contents