AC300 Series Vector Control Inverter Manual
connect fault
● Keyboard component
damage.
● Baud rate not right.
RS485
● Communication connection
18
communicatio
not right.
n fault
● Communication format not
right.
● Parameter copy
Parameter
communication is fault.
E.CPE
copy fault
● Copy keyboard is not match
the inverter.
●
The expansion card
Expansion
communicates with the inverter
card
-
for timeout;
connection is
●
The expansion card does not
abnormal
match the drive.
PG card
●
PG card and inverter
27
connection is
connection failure
abnormal
●
PID feedback disconnection
alarm upper limit is set
improperly
●
PID feedback disconnection
29
PID feedback
alarm lower limit is set
/66
fault
improperly
●
Lose PID feedback wiring
●
Feedback sensor failure
●
Feedback input loop fault
Initial position
31
angle learning
● Check motor parameters
failed
Speed
●Checkout time or check level
32
deviation is
setting is unreasonable
/70
too large
● Motor parameter is abnormal
● FA.27/FA.28 parameter
33
Speed
setting is abnormal
/71
protection
● Motor parameter is abnormal
Fault Diagnoses and Processing
● Seek support from factory.
● Set right Baud rate
● Check communication wiring
● Check Communication
format
● Check wire.
● Select the specified external
keyboard model.
●
Check the connector and
re-plug the cable;
●
Use the expansion card of
the specified model.
●
Check connection
● Confirm the sensor status
and replace the sensor if it is
damaged.
● Correct wiring
● Confirm the set values of
F11.27 and F11.28
● Check the motor parameters;
● Learn after the motor is
stationary;
● Seek technical support from
manufacturers.
● Check the motor parameters
and re-learn again;
● Check the F10.24/F10.25
parameter settings;
● Seek technical support from
manufacturers.
● Check the motor parameters
and re-learn again;
● Check the F10.27/F10.28
36
AC300 Series Vector Control Inverter Manual
● Check the F6 group vector
control parameters
34
Load
● The checkout time or check
/67
protection 1
level setting is unreasonable
35
Load
● The checkout time or check
/68
protection 2
level setting is unreasonable
CPU
36
● CPU timing timeout
time out
GPS lock
72
● GPS timing timeout
machine
GPS
● GPS communication
73
disconnection
disconnection
Fan short
40
● Fan short circuit
circuit
Motor short to
39
● Motor short circuit to ground
ground
Fault Diagnoses and Processing
parameter settings;
● Check the F10.18/F10.19
parameter settings;
● Check the F10.20/F10.21
parameter settings;
● Seek technical support from
manufacturers.
● Seek technical support from
manufacturers.
● Whether the GPS expansion
card is connected properly;
● GPS communication card is
arrears;
● Seek technical support from
manufacturers.
● Check if the fan is smooth
● Check if the motor is shorted
to ground
37