This chapter just provides function parameter table. Specifications refer to AC200 technical manual or inquiry the company.
"●": Parameter can be changed in the running state.
"〇": Parameter can't be changed in the running state.
"×": Parameter can be read only.
"–": Factory setting parameter, only factory can set.
"※": Parameter is related to the model.
4.1 Basic parameters
NO.
Function description
F00.00
Motor control mode
F00.01
Reserved
F00.02
Run command channel
Frequency given
F00.03
source channel A
Frequency given
F00.04
source channel B
Frequency channel B
F00.05
reference source
Frequency given
F00.06
source selection
Running Command
F00.07
Binding
Chapter 4 Function Parameter Table
Range of settings and definition
Asynchronous motor control mode:
0: V/F control
3: High-performance VC without PG
4: High-performance VC with PG
Synchronous motor control mode:
6: High-performance VC without PG
7: VC with PG
Other control:
8:Voltage frequency separation output
1/2/5: Reserved
0: Keyboard control
1: Terminal control
0: Keyboard number given
1: Reserved
2: Voltage/Current analog AI1 given
3: Voltage/Current analog AI2 given
4: Reserved
5: Terminal pulse PUL given
6: RS485 communication given
7: Terminal UP/DW control
8: PID control given
9: Program control (PLC) given
10: Optional card
11: Multi-steps speed given
0: Max. output frequency as reference source
1: Set frequency of channel A as reference source
0: Channel A
1: Channel B
2: Channel A+Channel B
3: Channel A-Channel B
4: Max. value of Channel A and Channel B
5: Min. value of Channel A and Channel B
LED"0"digit: keyboard command instruction binding
LED"00"digit: terminal command instruction binding
LED"000"digit: communication command instruction
binding
LED"0000"digit: optional card command instruction
binding
0 : no binding
1 : keyboard number given frequency
2: RS485 communication control
3: Reserved
9
Factory
Fea
Address
default
ture
0
0x000
〇
0x001
0
●
0x002
0
●
0x003
1
●
0x004
0
●
0x005
0
●
0x006
0000
●
0x007