AC300 series vector control inverter manual
Guidance on disassembly and waste disposal
The package of the inverter can be reused. Please keep the package for future
use or return it to the manufacturer.
The removed metal parts can recyclable.
Some devices may badly affect the environment, such as electrolytic capacitors,
please handle devices in accordance with the requirements of the environmental
protection department.

1.2 Technical Specifications

Table 1-1: Technical Specifications
Items
Single phase 220V
Voltage, frequency
Three phase 220V
Three phase 1140V 50/60Hz
voltage unbalance rate:<3%; Frequency:±5%; aberration rate: as
Powerin
Allowable fluctuations
IEC61800-2 required
put
Inrush current
Lower than rated current
Power factor
≥0.94(with DC reactor)
Efficiency
≥96%
Output voltage
Output under rated condition: 3 phase, 0~input voltage, inaccuracy<5%
Output frequency
G/P type:0~600Hz
range
Output frequency
Max frequency ±0.5%
Output
G type: 150% rated current/1 min, 180% rated current/10s, 200% rated
current/0.5s
Overload capacity
P type: 120% rated current/1 min, 140% rated current/10s, 150% rated
current/0.5s
Motor control mode
V/F without PG , VC without PG, V/F with PG, VC with PG
Modulation mode
Optimized SVPWM mode
Carrier frequency
0.7~16.0kHz
Main
Speed control range
VC without PG: rated load 1:100; VC with PG: rated load 1:1000
Controlper
formance
Steady speed
VC without PG: ≤2% rated synchronized speed; VC with PG: ≤0.05% rated
accuracy
synchronized speed
VC without PG: when 0.5Hz, 150% rated torque; VC with PG: when 0Hz,
Starting torque
200% t d t
Torque response
VC without PG: ≤20ms; VC with PG: ≤10ms
Overview
Specifications
50/60Hz
Three phase 380V 50/60Hz
50/60Hz
Three phase 660V 50/60Hz
Three phase 480V 50/60Hz
4
AC300 series vector control inverter manual
Frequency accuracy
Digit setting: max frequency×±0.01%; Analog setting: max frequency×±0.2%
Frequency resolution
Digit setting: 0.01Hz; Analog setting: max frequency×0.05%
Starting frequency:0.00~50.00Hz; Braking time:0.0~60.0s; Braking
DC braking capacity
current:0.0~150.0% rated current
Torque boost
Auto torque upgrade 0.0%~100.0%; Manual torque upgrade 0.0%~30.0%
it
4 modes: one linearity torque characteristic curve ,one self-setting V/F curve
V/F curve
mode, one drop torque characteristic curve (1.1- 2.0 powers),and square V/F
curve mode.
2 modes: linear Acceleration/Deceleration and S curve
Acceleration/Deceler
Acceleration/Deceleration. 4 sets of ACC/DEC, time unit 0.01s selectable,
ation curve
longest time: 650.00s.
Rely on power supply voltage compensate function, while motor rated
Rated output voltage
voltage is 100%, set it at the range of 50-100%(output can not over input
voltage).
Voltage
While power supply voltage fluctuates, it can auto-keep constant output
auto-adjustment
voltage.
Auto energy-saving
While under V/F control mode, according to load situation, auto-optimize
running
output voltage to save energy.
Basic
Auto-limit current
Auto-limit the current while running to prevent over current break trouble.
functions
Instant power off
While instant power off, realize continual operation by bus voltage control.
treatment
PID control, speed track, power off restart, jump frequency, upper/lower
Standard functions
frequency limit control, program operation, multi- speed, RS485, analog
output, frequency impulse output.
Keyboard digital setting, Analog voltage/current terminal AI1, Analog
Frequency setting
voltage/current terminal AI2, Communication given and multi-channel
channels
terminal selection, Main and auxiliary channel combination, expansion card,
supporting different modes switch
Voltage/Current Terminal AI1, Voltage/Current Terminal AI12, Communication
Feedback input
given, Low-speed pulse input PUL, extension card
channel
Running command
Operation panel given, external terminal given, communication given,
channel
expansion card given
Input command
Start, stop, FWD/REV, JOG, multi-step speed, free stop, reset, ACC/DEC
signal
time selection, frequency given channel selection, exterior fault alarm.
Exterior output
1 relay output, 1 collector output, 1 AO output: 0~10V output or 4~20mA
signal
output, or frequency pulse output
Overvoltage, under-voltage, current limit, over-current, overload, electric
Protection function
thermal relay, overheat, overvoltage stall, data protection, rapid speed
protection, input/output phase failure protection
Overview
5