CB-7080 & CB-7080D Counter/Timer User's Guide
$AAB
Description
: Read input mode. Refer to
information.
Syntax
: $AAB[chk](cr)
$
AA
B
[chk]
(cr)
:
Response
Valid response
Invalid response
no response
!
?
AA
S=0
S=1
S=2
S=3
[chk]
(cr)
Examples
:
Counter/frequency channel 0 is non-isolated, channel 1 is non-isolated:
command:
response:
Counter/frequency channel 0 is isolated, channel 1 is isolated:
command:
response:
Counter/frequency channel 0 is non-isolated, channel 1 is isolated:
command:
response:
"Counter/Frequency input mode
A delimiter character
2-character HEX module address, from 00 to FF
2-character checksum. If checksum is disabled, no [chk]
0x0D
!AAB[chk](cr)
?AA[chk](cr)
Syntax error, communication error or address error
A delimiter character indicating a valid response
A delimiter character indicating an invalid response
2-character HEX module address
channel 0 is non-isolated, channel 1 is non-isolated.
channel 0 is isolated, channel 1 is isolated.
channel 0 is non-isolated, channel 1 is isolated.
channel 0 is isolated, channel 1 is non-isolated.
2-character checksum. If checksum is disabled, no [chk]
0x0D
$01B(cr)
!010(cr)
$02B(cr)
!021(cr)
$03B(cr)
!032(cr)
selection" on page 1-6 for more
2-31
$AAB
Need help?
Do you have a question about the CB-7080 and is the answer not in the manual?