CB-7080 & CB-7080D Counter/Timer User's Guide
@AAPN(data)
Description
: Set the preset value of counter. The $AA6 command can reset counter to preset value. Refer to
"Preset value
setting" for more information.
Syntax
: @AAPN(data)[chk](cr)
@
AA
P
N=0
N=1
(data)
[chk]
(cr)
Response
:
Valid response
invalid response
no response
!
?
AA
[chk]
(cr)
:
Examples
The preset value of counter 0 is FFFF0000h:
command:
response:
The preset value of counter 1 is 0000FFFFh:
command:
response:
A delimiter character
2-character HEX module address, from 00 to FF
Counter 0
Counter 1
8-character HEX value.
2-character checksum. If checksum is disabled, no [chk]
0x0D
!AA(data)[chk](cr)
?AA[chk](cr)
Syntax error, communication error or address error
A delimiter character indicating a valid response
A delimiter character indicating an invalid response
2-character HEX module address
2-character checksum. If checksum is disabled, no [chk]
0x0D
@01P0FFFF0000(cr)
!01(cr)
@02P10000FFFF(cr)
!02(cr)
2-45