4.4

PLACE OF INSTALLATION

WARNING !
UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL only..
The UPS should be installed in a restricted area where only qualified personnel should be admitted.
The place of installation should be clean, dust-free, and provided with proper ventilation or air-
conditioning.
Verify for sufficient floor load capacity (see Section 4.1.1).
We strongly advice that the ambient temperature should not exceed 20° to 25°C / 68° to 77°F (max.
35°C / 95°F). See Section 4.5.
NOTE !
Insufficient space on both sides of the UPS in respect to the wall can cause a
dangerous increase of the internal operating temperature.
Fig. 4.4-1 LP 33 Series positioning
Fig. 4.4-2 RPA parallel system positioning
NOTE !
Operating temperature is very important for valve regulated battery (maintenance
free).
Operation at temperatures higher than 20°C (68°F) will reduce life expectancy.
Respect the prescription VDE 0510, those of the battery supplier and other local
standards.
The installation and cabling of the battery must be done by qualified people.
Modifications reserved
OPM_LPS_33E_10K_30K_4GB_V030.doc
LP 33 Series positioning
For easier access in case of maintenance
operation and for a free circulation around the
cabinet, we recommend to maintain the
following minimum distances:
Right & left side:
100 mm (4")
Rear side:
50 mm
Top of the UPS:
300 mm (12")
Right & left side:
200 mm (8")
Rear side:
50 mm
Top of the UPS:
300 mm (12")
NOTE !
Both lateral sides of the UPS MUST BE
ACCESSIBLE at any time for repair or
maintenance.
(2")
(2")
Page 23/85
Operating Manual LP 33 Series / 10-20-30 kVA